OPTIONAL ANNUAL REPORT TEMPLATE
Drinking-Water System Number: |
220004162 |
Drinking-Water System Name: |
|
Drinking-Water System Owner: |
The
Corporation of the Town of |
Drinking-Water System Category: |
Large
Municipal Residential System |
Period being reported: |
|
·
·
·
www.markham.ca Does your Drinking-Water System serve more than 10,000 people? Yes [x] No [ ] Is your annual report available to the public at no charge on a web site on the Internet? Yes [x] No [ ] Location where Summary Report required under O. Reg. 170/03 Schedule 22 will be available for inspection. |
Complete for all other
Categories. Number of Designated Facilities served: Did you provide a copy of your annual report to all Designated Facilities you serve? Yes [ ] No [ ] Number of Interested Authorities you report to: Did you provide a copy of your annual report to all Interested Authorities you report to for each Designated Facility? Yes [ ] No [ ] |
Note: For the following tables below, additional rows or columns may be added or an appendix may be attached to the report |
List all Drinking-Water Systems (if any), which receive all of their drinking water from your system:
Drinking Water System Name |
Drinking Water System Number |
|
|
Did you provide a copy of your annual report to all Drinking-Water System owners that are connected to you and to whom you provide all of its drinking water?
Yes [ ] No [ ]
Indicate how you notified system users
that your annual report is available, and is free of charge.
[x] Public access/notice via the web
[x] Public access/notice via Government Office
[x] Public access/notice via a newspaper
[x] Public access/notice via Public Request
[ ] Public access/notice via a Public Library
[ ] Public access/notice via other method _______________________________________
Describe your Drinking-Water System
Markham is a distribution only system, without pumping and storage facilities.
Markham’s
drinking water within the distribution system is tested for standard
parameters, in compliance with the
List all water treatment chemicals used over this reporting period
Not applicable |
Were any significant expenses incurred to?
[x]
Install required equipment
[x]
Repair required equipment
[x]
Replace required equipment
Watermain cement relining (Watermain rehabilitation) =$1,043,780.00
Cathodic Protection of Iron Watermains =$449,965.00
Water meter replacement/Upgrades =$1,115,311.00
Watermain replacement =$2,100,646.25
Watermain replacement design for 2010 =$100,000.00
Water system condition rating system =$64,105.00
Watermain repair =$183,333.61
Provide details on the notices submitted in accordance with subsection 18(1) of the Safe Drinking-Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to Spills Action Centre
Incident Date |
Parameter |
Result |
Unit of Measure |
Corrective Action |
Corrective Action Date |
2009-06-30 (AWQI # 88881) |
Total coliform |
P |
P/A |
Flush Mains and Resample |
2009-06-30 |
2009-06-30 (AWQI # 88889) |
Total coliform |
P |
P/A |
Flush Mains and Resample |
2009-06-30 |
2009-06-30 (AWQI # 88899) |
Total coliform |
P |
P/A |
Flush Mains and Resample |
2009-06-30 |
2009-07-07 (AWQI #89095) |
Total coliform |
P |
P/A |
Flush Mains and Resample |
2009-07-07 |
2009-07-28 (AWQI #90007) |
Total coliform |
P |
P/A |
Flush Mains and Resample |
2009-07-28 |
2009-08-11 (AWQI # 90395 |
Total coliform |
P |
P/A |
Flush Mains and Resample |
2009-08-11 |
2009-08-11 (AWQI # 90378 |
Total coliform |
P |
P/A |
Flush Mains and Resample |
2009-08-11 |
2009-08-12 (AWQI #90453) |
Total coliform – 2 samples |
1 3 |
CFU |
Flush Mains and Resample |
2009-08-12 |
2009-09-10 (AWQI # 93119) |
Low Chlorine |
0.14 |
mg/L |
Flush Hydrant until a level above 0.74 mg/L was achieved |
2009-09-10 |
2009-10-23 (AWQI #92031) |
Fecal streptococci |
P |
P/A |
Flush Mains and Resample |
2009-10-23 |
Microbiological
testing done under the Schedule 10, 11 or 12 of Regulation 170/03, during this
reporting period.
|
Number of Samples |
Results (min #)-(max #) |
(min #)-(max #) |
Number of HPC Samples |
(min #)-(max #) |
Raw |
|
|
|
|
|
Treated |
|
|
|
|
|
Distribution |
2517 |
<1 |
<1 – 3 |
1277 |
<1 - 320 |
Operational testing done under Schedule 7, 8 or 9 of Regulation 170/03 during the period covered by this Annual Report.
NOTE: For continuous monitors use
8760 as the number of samples. |
Number of Grab Samples |
(min #)-(max #) |
||
Turbidity |
|
|
||
Chlorine |
5891 |
0.14 mg/L - 1.34 mg/L |
||
Fluoride (If the DWS provides fluoridation) |
0 |
Tested in 2005 (done every 5 years) |
NOTE:
Record the unit of measure if it is not milligrams
per litre. |
Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument.
Date of legal instrument issued |
Parameter |
Date Sampled |
Result |
Unit of Measure |
|
|
|
|
|
|
|
|
|
|
Summary of Inorganic parameters tested during this reporting period or the most recent sample results
Parameter
|
Sample
Date
|
Result Value |
Unit
of Measure
|
Exceedance
|
Antimony |
May 29/09 |
0.0006 |
mg/L |
No |
Arsenic |
May 29/09 |
0.0011 |
mg/L |
No |
Barium |
May 29/09 |
0.0217 |
mg/L |
No |
Boron |
May 29/09 |
0.027 |
mg/L |
No |
Cadmium |
May 29/09 |
<0.0001 |
mg/L |
No |
Chromium |
May 29/09 |
<0.0001 |
mg/L |
No |
*Lead |
Not applicable |
|
|
|
Mercury |
May 29/09 |
<0.02 |
mg/L |
No |
Selenium |
May 29/09 |
0.0010 |
mg/L |
No |
Sodium |
Not applicable |
|
|
|
Uranium |
May 29/09 |
0.0003 |
mg/L |
No |
Fluoride |
Not applicable |
|
|
|
Nitrite |
Dec 02/09 |
<0.001 |
mg/L |
No |
Nitrate |
Dec 02/09 |
0.336 |
mg/L |
No |
*only for drinking water systems testing under Schedule 15.2; this
includes large municipal non-residential systems, small municipal
non-residential systems, non-municipal seasonal residential systems, large
non-municipal non-residential systems, and small non-municipal non-residential
systems
Summary of lead testing under Schedule 15.1 during this reporting period
(applicable
to the following drinking water systems; large municipal residential systems, small
municipal residential systems, and non-municipal year-round residential
systems)
Location Type |
Number of Samples |
(min#) – (max #) |
Number of Exceedances |
Plumbing |
311 x 2 = 622 |
<0.0001 – 0.0097 |
0 |
Distribution |
173 |
<0.0001 – 0.0033 |
0 |
Summary of Organic parameters sampled during this reporting period or the most recent sample results
Parameter |
Sample
Date
|
Result Value |
Unit
of Measure
|
Exceedance
|
Alachlor |
|
<0.4 |
µg/L |
No |
Aldicarb |
|
<6.0 |
µg/L |
No |
Aldrin + Dieldrin |
|
<0.006 |
µg/L |
No |
Atrazine + N-dealkylated metobolites |
|
<0.2 |
µg/L |
No |
Azinphos-methyl |
|
<0.3 |
µg/L |
No |
Bendiocarb |
|
<3.0 |
µg/L |
No |
Benzene |
|
<0.1 |
µg/L |
No |
Benzo(a)pyrene |
|
<0.01 |
µg/L |
No |
Bromoxynil |
|
<0.4 |
µg/L |
No |
Carbaryl |
|
<3.0 |
µg/L |
No |
Carbofuran |
|
<3.0 |
µg/L |
No |
Carbon Tetrachloride |
|
<0.2 |
µg/L |
No |
Chlordane (Total) |
|
<0.006 |
µg/L |
No |
Chlorpyrifos |
|
<0.2 |
µg/L |
No |
Cyanazine |
|
<0.3 |
µg/L |
No |
Diazinon |
|
<0.2 |
µg/L |
No |
Dicamba |
|
<0.4 |
µg/L |
No |
1,2-Dichlorobenzene |
|
<0.1 |
µg/L |
No |
1,4-Dichlorobenzene |
|
<0.1 |
µg/L |
No |
Dichlorodiphenyltrichloroethane (DDT) + metabolites |
|
<0.008 |
µg/L |
No |
1,2-Dichloroethane |
|
<0.1 |
µg/L |
No |
1,1-Dichloroethylene (vinylidene chloride) |
|
<0.3 |
µg/L |
No |
Dichloromethane |
|
<0.5 |
µg/L |
No |
2-4 Dichlorophenol |
|
<0.7 |
µg/L |
No |
2,4-Dichlorophenoxy acetic acid (2,4-D) |
|
<0.8 |
µg/L |
No |
Diclofop-methyl |
|
<0.4 |
µg/L |
No |
Dimethoate |
|
<0.3 |
µg/L |
No |
Dinoseb |
|
<0.5 |
µg/L |
No |
Diquat |
|
<1.0 |
µg/L |
No |
Diuron |
|
<3.0 |
µg/L |
No |
Glyphosate |
|
<25 |
µg/L |
No |
Heptachlor + Heptachlor Epoxide |
|
<0.008 |
µg/L |
No |
Lindane (Total) |
|
<0.005 |
µg/L |
No |
Malathion |
|
<0.2 |
µg/L |
No |
Methoxychlor |
|
<0.009 |
µg/L |
No |
Metolachlor |
|
<0.2 |
µg/L |
No |
Metribuzin |
|
<0.3 |
µg/L |
No |
Monochlorobenzene |
|
<0.1 |
µg/L |
No |
Paraquat |
|
<1.0 |
µg/L |
No |
Parathion |
|
<0.2 |
µg/L |
No |
Pentachlorophenol |
|
<0.4 |
µg/L |
No |
Phorate |
|
<0.2 |
µg/L |
No |
Picloram |
|
<0.7 |
µg/L |
No |
Polychlorinated Biphenyls(PCB) |
|
<0.02 |
µg/L |
No |
Prometryne |
|
<0.2 |
µg/L |
No |
Simazine |
|
<0.2 |
µg/L |
No |
THM (NOTE: show latest annual average) |
|
16.8 |
µg/L |
No |
Temephos |
|
<3 |
µg/L |
No |
Terbufos |
|
<0.2 |
µg/L |
No |
Tetrachloroethylene |
|
<0.3 |
µg/L |
No |
2,3,4,6-Tetrachlorophenol |
|
<0.5 |
µg/L |
No |
Triallate |
|
<4.0 |
µg/L |
No |
Trichloroethylene |
|
<0.1 |
µg/L |
No |
2,4,6-Trichlorophenol |
|
<0.5 |
µg/L |
No |
2,4,5-Trichlorophenoxy acetic acid (2,4,5-T) |
|
<0.5 |
µg/L |
No |
Trifluralin |
|
<0.006 |
µg/L |
No |
Vinyl Chloride |
|
<0.2 |
µg/L |
No |
List any Inorganic or Organic parameter(s) that
exceeded half the standard prescribed in Schedule 2 of
Parameter |
Result Value |
Unit of Measure |
Date of Sample |
|
|
|
|
|
|
|
|